MIQ Constant-Watt Industrial Heating Cable - Thermon

Temperature Maintenance: up to 932⁰C

Thermon MIQ-Series-Constant-Watt-Heating-Cable
PDF

The Thermon MIQ Constant-Watt Industrial Heating Cable represents a pinnacle in high-performance mineral-insulated heating technology, catering to applications that demand elevated temperature maintenance, exposure, and/or high watt density – surpassing the constraints of thermoplastic insulated cables. Renowned for its versatility, MIQ cables offer resistance configurations capable of providing effective tracing for pipes extending up to an impressive 1.6 kilometers (1 mile) from a single power supply point.

At the core of MIQ’s robust design is the use of Alloy 825, a high nickel/chromium alloy meticulously selected for its exceptional suitability in high-temperature service. This alloy ensures remarkable resistance to stress corrosion in challenging environments characterized by chloride, acid, salt, and alkaline elements. This feature makes MIQ cables particularly well-suited for demanding industrial settings where resilience to corrosive conditions is paramount.

Notably, MIQ mineral-insulated heating cables have received approvals for usage in both ordinary (nonclassified) areas and hazardous (classified) areas, emphasizing their adaptability and safety compliance. This comprehensive package of high-performance capabilities, durability through Alloy 825 construction, and safety certifications establishes MIQ Constant-Watt Industrial Heating Cable as a reliable and indispensable solution for applications requiring precision and resilience in high-temperature scenarios.

MIQ Industrial Heating Cable Construction

  1. Solid alloy or copper conductor(s)
  2. Compacted magnesium oxide insulation
  3. Seamless alloy 825 sheath

MIQ Industrial Heating Cable Specifications

  • Rated voltage 300 and 600 Vac
  • Max. maintenance temperature 932°F (500°C)
  • Max. Power-off continuous exposure temperature 1,112°F (600°C)
  • Max. watt density up to 80 w/ft (262 w/m)
  • Minimum installation temperature -76°F (-60°C)
  • Minimum bend radius 6 x cable O.D.